FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
If the operation panel has not been operated for the time set in Pr.1048 Display-off waiting time, the display-off mode is enabled and the "MON" LED blinks s... More Details >>
- No:21075
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Set Pr.79 (Operation mode) setting value to "0", "2", or "6", Pr.340 (Communication startup mode selection) other than the setting value, Pr.542 (Station num... More Details >>
- No:21896
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>
- No:21722
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
The conventional plug-in option (FR-A7[][]) cannot be used. Use the dedicated plug-in option (FR-A8[][]). More Details >>
- No:21114
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , Plug-in Options , FREQROL-F800
-
The 800 series supports the multiple rating. Thus, the rated current of the corresponding motor is 40% or higher of the inverter rated current. (Using a moto... More Details >>
- No:21085
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
The undervoltage warning of the inverter is judged based on the voltage of the main circuit as follows. Power failure only at the main circuit: Output an und... More Details >>
- No:20853
- Release Date:2018/08/22 16:24
- Category: FREQROL-A800 , FREQROL-F800
-
Turn ON the monitor command RYC. More Details >>
- No:21826
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
291-300 of Total 1292