FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
When auto tuning completes normally, the setting value of Pr.96 (Auto tuning setting/status) is changed to "3". When it is not changed, check the set paramet... More Details >>
- No:21353
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700PJ
-
Normally, the auto tuning condition depends on the combination of the inverter and motor (including wiring to the motor), perform auto tuning each time. The ... More Details >>
- No:21293
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700PJ
-
Auto tuning can help to apply appropriate voltage to the load and decrease the current. Since the electronic thermal O/L relay trips, check that the rated mo... More Details >>
- No:21292
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700PJ
-
Approximately 2 years when the FR-LU08 is not energized and the real-time clock function is enabled. More Details >>
- No:21084
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options , FREQROL-A800 , FREQROL-F800
-
No. They can be connected with the connection cable (FR-CB20[]). [] indicates cable length (1 m, 3 m, 5 m). More Details >>
- No:21081
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options , FREQROL-A800 , FREQROL-F800
-
Yes. More Details >>
- No:21063
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options , Others , FREQROL-B
-
SC type (with an encoder) of the SF-PR
Use the FR-V7CBL5/15/30 as using it with the vector motor SF-V5RU connection. More Details >>
- No:20867
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options , Others , Peripheral devices
-
Proper use of AC reactor and DC reactor
1. ACL has the input power factor of approximately 90% and DCL has the input power factor of approximately 95%. Therefore, DCL has a higher input power facto... More Details >>
- No:21949
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
You can do so by setting Pr.73 to "10" or "11". (For A700/F700 (P), supply negative input to the terminal 1.) More Details >>
- No:21908
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Input 4 words, output 4 words for version 1. 2, 4, and 8 times for version 2. More Details >>
- No:21874
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
301-310 of Total 1306