FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
At power-ON, the signal turns ON for a moment to perform a converter initial reset. More Details >>
- No:21156
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , Options
-
They are not output while the motor is coasting even under Vector control. More Details >>
- No:21158
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700
-
"E.OSD" occurs when the rotation speed is not decreased for one second despite the start command (STF, STR) is turned OFF. More Details >>
- No:21159
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700
-
Check the setting value of Pr.37 (Speed display). When the machine speed is set, Pr.811 is disabled. Change the setting to the rotation speed. More Details >>
- No:21161
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700
-
Countermeasure against harmonics
When the high power factor converter is installed, you can use the conversion coefficient of K5 = 0 for calculation. In accordance with the harmonic suppress... More Details >>
- No:21398
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Others
-
Notes on using single-phase 200 V
With the single-phase 200 V input specifications, the input cable current increases. Therefore, choose larger power supply capacity and NF/MC than three-phas... More Details >>
- No:21406
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Indication of potentiometer on operation panel
The potentiometer on the operation panel is initially calibrated so that the maximum indication is slightly over 60 Hz with the potentiometer turned to the m... More Details >>
- No:21427
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Direct driven start by power supply
The warning "Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter." is indicated in the precautions at the be... More Details >>
- No:21458
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Since the inverter power supply uses the single-phase input, you cannot use a 0.75K inverter with a 0.6 kW motor to draw the maximum ability of the motor. To... More Details >>
- No:21470
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
Controlling multiple VVVFs via communication from personal computer
To control multiple inverters using arbitrary signals (4 to 20 mA) simultaneously, it is recommended to connect the signals (4 to 20 mA) in series. (This doe... More Details >>
- No:21491
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
361-370 of Total 1292