FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Basically it is not possible due to the operation command source.However, if Pr.77 (Parameter write selection) is set to "2", you can use both the FR-PA07 an... More Details >>
- No:21698
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Connecting it causes no problem. More Details >>
- No:21671
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700PJ
-
You cannot reuse the parameter unit (FR-PU01) for the FREQROL-Z series, the parameter unit (FR-PU02) for the FREQROL-A200 and A100 series, and the parameter ... More Details >>
- No:21654
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-V200
-
Can a single potentiometer operate two speed controller?
A single potentiometer cannot operate two speed controller. Reason: Since the control circuit and main circuit of the SC-A speed controller are not insulated... More Details >>
- No:21578
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , SC-A
-
When the heat sink is outside, since the heat sink and fan are not waterproof, you need to enclose them so that they are not exposed to the spray of water. More Details >>
- No:21435
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
-
Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>
- No:21330
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>
- No:21245
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
The corresponding bit (RYB) can be used when a function other than reset is assigned to the RES terminal, but it cannot be used as the reset function. Use RY... More Details >>
- No:21142
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , Plug-in Options
-
The conventional plug-in option (FR-A7[][]) cannot be used. Use the dedicated plug-in option (FR-A8[][]). More Details >>
- No:21114
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , Plug-in Options , FREQROL-F800
-
When Pr.414 is set to "1" and Pr.388 is set to "0", the PLC function is not enabled unless both the SQ signal from communication and the SQ signal from the e... More Details >>
- No:21073
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800