The operation command source is automatically transferred to the connected FR-PU07 or FR-PA07. More Details >>
- No:21700
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
From Z100 to A520: Use the FR-AAT01 to replace the Z100 with the A520. From Z100 to E520: No attachment is available since E520 is a new series. From Z100 to... More Details >>
- No:21447
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options , FREQROL-Z100
-
Even though the maximum frequency setting is changed using CC-Link, the running frequency is not changed. By writing the set frequency to the remote register... More Details >>
- No:21346
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Connect the brake resistor to the terminal P and terminal PR. (For the FR-A700-7.5K or lower, remove the jumper of the terminals PR and PX.) Do not remove th... More Details >>
- No:21333
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700PJ
-
Yes, they are the same. More Details >>
- No:21010
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800 , FREQROL-E700
-
DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>
- No:20905
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
1. By setting Pr.158 (Terminal AM function selection) to "21" (Reference voltage output), 10 V is output from the terminal AM.2. Read Pr.901 in the PU operat... More Details >>
- No:21936
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-A200 , FREQROL-A100
-
You can do so by setting Pr.339 (Communication speed command source) = 1 (external). More Details >>
- No:21881
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Set Pr.338 (Operation command source) to "1" (external terminal).Set Pr.339 (Speed command source) to "0" (communication).Check the setting of Pr.79 for oper... More Details >>
- No:21869
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Only the operation command source is switched to the FR-A07 and the inverter operation panel does not turn off. (Setting from the inverter operation panel be... More Details >>
- No:21699
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ