Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
You can vary the carrier frequency within the range of 0.7 to 14.5 kHz, and it is initially set to 1 kHz that generates low noise and leakage current. You ca... More Details >>
- No:21607
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A024
-
1. Such a behavior does not usually happen. (1) The operation command (STF) is not input, contact faults are present, or wire is broken. (2) The output shu... More Details >>
- No:21552
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Noise filtering and harmonics suppression are different matters and you need to install the line noise filter (FR-BSF01) against noise and DCL (FR-BEL) again... More Details >>
- No:21548
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Options
-
Acquisition of pressure-resistant explosion-proof certification
The test institutes assigned by the Minister of Health, Labour and Welfare (National Institute of Occupational Safety and Health and Technology Institution o... More Details >>
- No:21510
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-B
-
Current value on input side and output side
1. When slight imbalance (approximately 5%) is present with the inverter power supply voltage, the inverter input current can get imbalanced significantly. I... More Details >>
- No:21476
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-A200
-
Difference between SU (up to frequency) and FU (frequency detection)
- SU signal (up to frequency signal)This signal is output when the inverter output frequency reaches the set frequency (the frequency the inverter is require... More Details >>
- No:21436
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
The high speed command (multi-speed command) is prioritized over the frequency setting potentiometer. It is OK if these are both input simultaneously. When t... More Details >>
- No:21424
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-U100
-
The operation panel FR-PA02 requires the optional FR-E5P (control panel rear cover and adapter set) and connection cable FR-CB20□. Check that Pr.146 (Built-i... More Details >>
- No:21367
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Real sensorless vector control
For tuning of a single motor with no load, set Pr.96 to "101". When a load is connected, set Pr.96 to "1" (without motor rotation). Since Real sensorless vec... More Details >>
- No:21325
- Release Date:2018/08/22 16:27
- Category: FREQROL-A700
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>