No. (Using the copy function causes an error.) Use the FR-DU08 when performing the copy function of the operation panel. More Details >>
- No:21118
- Release Date:2018/08/22 16:26
- Category: FREQROL-A800 , Options , FREQROL-F800
-
The sine wave filter can be applied only under V/F control. When Pr.72 PWM frequency selection is set to 25, V/F control is set automatically. The applicable... More Details >>
- No:21068
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options , FREQROL-A800 , FREQROL-A700
-
No, it cannot. The standard operation panel (FR-DU08) can be connected to the face of the board by using the FR-ADP (operation panel connection connector) an... More Details >>
- No:20898
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options , FREQROL-A800 , FREQROL-F800
-
- Both 200 V and 400 V can be used only with the capacity 22 kW or higher. - The rated current (capacity) is derated. (For the detail, refer to the Instructi... More Details >>
- No:20802
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
You can do so by setting Pr.73 to "10" or "11". (For A700/F700 (P), supply negative input to the terminal 1.) More Details >>
- No:21908
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Up to 42 units can be connected. (When only inverters are connected) More Details >>
- No:21873
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Since the percent value read by the calibration parameter C7 indicates that the voltage of 10 V is internally detected as 101.0%, use 101.0% as is.If you cha... More Details >>
- No:21740
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
The inverters FR-A200 and V200 do not support CC-Link. (The FR-A500 series supports CC-Link.) Use the open collector output and relay output card when combin... More Details >>
- No:21504
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-V200 , FREQROL-A200
-
Calculation of inverter acceleration and deceleration time
Refer to the Technical Sheet No.23 (Capacity Selection and Continuous Operation) for reference for selection. Optional capacity selection software is also pr... More Details >>
- No:22097
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
1. The 100% braking torque means the 100% motor rated torque. Do not consider the continuous regenerative driving based on the braking torque. Consider the r... More Details >>
- No:22023
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
401-410 of Total 1292