Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
No. You cannot connect it to multiple inverters.You can only connect a single personal computer to a single inverter via USB. More Details >>
- No:21710
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
You cannot disable the error display. The OC1 overcurrent alarm is displayed. The condition to display this alarm is that the main circuit power supply is OF... More Details >>
- No:21535
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
The inverter (FR-A520-5.5K) itself generates approximately 310 W of heat. This is the amount generated under the inverter rated current 100% load. Since the ... More Details >>
- No:21523
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Number of inverters that can be connected to a 20 A branch circuit breaker
The basic idea is the same, but the total capacity should be 3.7 kW. (The maximum capacity is also 3.7K.) More Details >>
- No:21508
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-A024
-
The high speed command (multi-speed command) is prioritized over the frequency setting potentiometer. It is OK if these are both input simultaneously. When t... More Details >>
- No:21424
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-U100
-
The current monitor displays the average value of the three-phase current. The three-phase voltage is not incorporated for the voltage monitor. The output vo... More Details >>
- No:21376
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
The FR-E700, D700, F700PJ may activate input phase loss protection "E.ILF" if the phase-to-phase voltage of the power supply has become largely unbalanced. More Details >>
- No:21339
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Yes. However, it is difficult to wind the twisted wires because they are thick. More Details >>
- No:21128
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , Options
-
No. (Using the copy function causes an error.) Use the FR-DU08 when performing the copy function of the operation panel. More Details >>