When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
- No:21327
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Supported model for FR-Configurator
For the models other than FR-A700/F700, use FR-Configurator (FR-SW3-SETUP-WJ). They are not supported by FR-Configurator (FR-SW2-SETUP-WJ). When you have the... More Details >>
- No:21313
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
FR-Configurator (FR-SW3-STUP-WJ) is the Japanese version. FR-Configurator (FR-SW3-SETUP-WE) is the English version. More Details >>
- No:21308
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>
- No:21285
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>
- No:21283
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
It is set to "1" (cooling fan ON-OFF control enabled). More Details >>
- No:21131
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-F700PJ
-
Sampling time of FR Configurator2
It depends on the mask count. It is approximately 0.125 [ms] (mask count: 1) to 20 [ms] (mask count: 30). More Details >>
- No:20950
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Engineering Software
-
Load characteristics fault detection
Only the V/F control is related with Pr.56. The motor torque is calculated from the current value (not Pr.56) and motor constant. For the V/F control, it is ... More Details >>
- No:20893
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-F800
-
From before, the QCPU has been used and each setting does not make a difference internally. Thus, the selection was reduced to the QCPU only. It can also be ... More Details >>
- No:20868
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Engineering Software
-
Insulation level of the MM-EFS
F class (155 deg C) More Details >>