Current input switching operation
With your setting, since Pr.60 assigns the OH function to the terminal PL, and terminals RL and SD are open, an external protection error occurs. (It does no... More Details >>
- No:21975
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-S500
-
Consideration on power supply capacity
The inverter's power supply capacity can be calculated using the following equation:Power supply capacity [kVA] = Motor output (kW)/(Motor efficiency × Inver... More Details >>
- No:22000
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Frequency adjustment using potentiometer
Since the inverter is initially set to 0 Hz for 0 V and 60 Hz for 5 V, you can calculate the frequency for a certain voltage value. The equation is "Output f... More Details >>
- No:22004
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Common terminals of control circuit
If you ground the common terminals of the control circuit, it is connected with the inverter's earthing and the inverter's noise may be input to the control ... More Details >>
- No:22037
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
It is protected not by observing the temperature directly, but by estimating it from the current value, output frequency, and carrier frequency. More Details >>
- No:20871
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A700
-
If Pr.361 = 0, the second terminal can be used as the line speed command when X114 is ON, and as the frequency setting value when X114 is OFF. If Pr.361 = 3,... More Details >>
- No:20891
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800
-
The FR-ASF may be damaged due to the surge voltage. More Details >>
- No:20989
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options
-
Parameter copy to the USB memory
Yes. Writing is available when the power supply specification or capacity is different. Note that setting values of the voltage relation is also overwritten ... More Details >>
- No:21013
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800
-
SW1DND-FRC2 (FR Configurator2)
SW1 is not supported because there is no product However, SW2 can be upgraded by entering the product ID. More Details >>
- No:21067
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Engineering Software
-
Since the FR-HC2 switches the TRM according to the power supply phase, it has a circuit that detects the power supply phase. "A phase is confirmed" when the ... More Details >>
- No:21154