FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Yes. Use the coated model, FR-A8NC-60. More Details >>
- No:20892
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL
-
It is available if the CC-Link option of the FR-A8NC is installed. More Details >>
- No:20894
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800
-
Yes. When Pr.9 = 0, turning is performed with the inverter rated current. Always set the rated motor current. More Details >>
- No:20897
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL
-
Terminal 2 input selector switch when the PTC thermistor is connected
When the DIP switch is changed to I, it does not operate normally because the internal resistance changes. More Details >>
- No:20901
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL
-
The count is resumed from 0. Thus, the times of the overflow is reset. More Details >>
- No:20902
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>
- No:20904
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Vector control cannot be selected unless Pr.862 is set to 1. (Only the first motor is supported in the motor setting of FR Configurator2.) More Details >>
- No:20908
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Engineering Software
-
Monitoring function of the FR-A800-R2R
No, they cannot be monitored when Pr.363 is other than "5". They are enabled only when Pr.363 = 5. More Details >>
- No:20915
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800
-
The frequency setting in the communication cannot be used together with FR-A8AX. The priority of the FR-A8AX is equal to the second terminal analog input and... More Details >>
- No:20917
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Plug-in Options
-
The torque limit setting is defined as an absolute value. Thus, when -100% is written to the torque limit, the torque is limited at 100%. More Details >>
- No:20920
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
41-50 of Total 1306