Operation panel extension cable
Yes, you can use the 10BASE-T cable (straight) with the E500. More Details >>
- No:22085
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Motor rated rotations per minute
The inverter is capable of output up to the maximum frequency. It is the matter of whether the motor used support high-speed operation. In the situation you ... More Details >>
- No:22099
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Influence on external measurement device
It is considered that malfunction of the measurement device is due to noise. Check the noise propagation route since the countermeasure depends on it. Some c... More Details >>
- No:22100
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Others
-
1. As the reactor (FR-HCL) is connected when connecting the FR-HC, do not connect the FR-BAL. 2. The noise filter can be connected to the input side of the F... More Details >>
- No:22101
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Operation at external operation/stop
It is recommended to turn OFF the start signals (STF and STR) when stopping the inverter.In this case, it is not probable that the motor rotates due to a cal... More Details >>
- No:22102
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-E500
-
Square wave input is not recommended since it can cause failures (for example, damage the diode bridge). More Details >>
- No:22106
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-E500
-
The power factor is 0.99 or more (at rated load). More Details >>
- No:20803
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
Not required. Select it according to the capacity of the vector motor used. More Details >>
- No:20804
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
No, you cannot use the safety stop function. More Details >>
- No:20817
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-B
-
The response delay time is 10 ms normally and 100 ms at startup. More Details >>
- No:20821
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Plug-in Options