Pr.59 is available in the products manufactured in October 1995 or later. Therefore, it cannot be read from the products manufactured before October 1995. More Details >>
- No:21170
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A024
-
It is one of other communication errors. The communication is not established. Check the communication settings. More Details >>
- No:21176
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , Engineering Software
-
The signals MRS and CS are required when the automatic bypass sequence enabled. More Details >>
- No:21187
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Check the setting value of Pr.73. Or check Pr.C4 (Terminal 2 frequency setting gain) for the percentage of the voltage that is actually applied. For the FR-E... More Details >>
- No:21356
- Release Date:2018/08/22 16:27
- Category: FREQROL-E700
-
Is the number of writing times of the parameter memory limited?
1. The limit of the parameter writing is 100,000 times. 2. Parameter error occurs. Since the data in the ROM may be broken, the inverter may become unavailab... More Details >>
- No:21385
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Providing thermal protection is better for your safety. When the brake transistor explodes, the brake transistor alarm (E.BE) is output. Consider a counterme... More Details >>
- No:21397
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
We recommend the "YM206RI 1 mA" analog ammeter. More Details >>
- No:21402
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
-
The FM output is the 1440 Hz, 1 mA pulse train output at full scale. You can input to the programmable controller if it has a pulse train input. A68AD does n... More Details >>
- No:21439
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
You can use an inverter for fan and pump with the compressor, but it is not recommended for an application that the motor load rapidly increases. More Details >>
- No:21443
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A100
-
Installing magnetic contactor on input side of inverter
Basically, there is no difference between the A200 and A500. For safer use, from the A500, it is recommended to completely shut off the power supply by turni... More Details >>
- No:21466
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500