1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
No. The "RUN" key on the FR-PA07 does not work.The start command is accepted from the external source. More Details >>
- No:21703
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
The following amount of heat is generated under the 100% load. (The same amount for both the 200 V and 400 V classes. The amount of heat generated by the bui... More Details >>
- No:21568
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-V200
-
Countermeasure against noise on input side
In general, the line noise filter (FR-BLF) is used against the power supply noise. The AC reactor also works. As other countermeasures:- Use a metal conduit ... More Details >>
- No:21517
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-A200
-
How can I calculate the processing torque from the measured power?
You can calculate the torque from the power. From the general equation: Pout = ωn × TT = (Pout × τ)/ωnPout: Measured valueωn: Actual motor shaft angular fre... More Details >>
- No:21475
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Others , FREQROL-A500
-
Connecting voltmeter to terminal AM
You can connect them in parallel. Connect the voltmeters in parallel, paying attention to the following: - The output current should not exceed the permissib... More Details >>
- No:21464
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
There is a 10 ms delay after the inverter recognizes the start command (STF OR STR) before it starts decelerating. The delay is 10 ms. A delay of 100 ms is i... More Details >>
- No:21445
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Indication of potentiometer on operation panel
The potentiometer on the operation panel is initially calibrated so that the maximum indication is slightly over 60 Hz with the potentiometer turned to the m... More Details >>
- No:21427
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Even though the maximum frequency setting is changed using CC-Link, the running frequency is not changed. By writing the set frequency to the remote register... More Details >>
- No:21346
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Real sensorless vector control
For tuning of a single motor with no load, set Pr.96 to "101". When a load is connected, set Pr.96 to "1" (without motor rotation). Since Real sensorless vec... More Details >>
- No:21325
- Release Date:2018/08/22 16:27
- Category: FREQROL-A700