FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
The FR-PU02-1 cannot be used with the FR-B3 series inverters. Use the FR-DU04 or FR-PU04. More Details >>
- No:21408
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-B
-
"E.OV3" is displayed when the voltage between the inverter terminals PN rises abnormally high while the inverter is decelerating or stopped. In this case, th... More Details >>
- No:21411
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
If you connect two frequency setting potentiometers to the terminals 5 and 10, the permissible current of 10 mA is exceeded, and you need to install 2 KΩ res... More Details >>
- No:21494
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Can I use digital operation panel FR-DU01?
You cannot use it with the standard and multi-function products. It can be connected to the dedicated PU operation type only. (Note that the FR-DU01 is an op... More Details >>
- No:21595
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-U100
-
Automatic restart after instantaneous power failure
The inverter has the automatic restart after instantaneous power failure function. By setting Pr.61 to other than "9999", the encoder detects the speed of th... More Details >>
- No:21642
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-V200
-
Its protective structure conforms to IP20.Therefore it is not waterproof. More Details >>
- No:21701
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others
-
You can install only one option card.If you want to use two types of cards, replace the inverter with the FR-A700 series.If you can use RS485 communication i... More Details >>
- No:21894
- Release Date:2018/08/22 16:29
- Category: FREQROL-E700
-
I want to display the speed on an analog meter.
As the inverter does not display the speed in m/min, let us explain using the speed display in r/min. In this case, set Pr.52 to "6" (operation panel display... More Details >>
- No:21944
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Fault contact state when input side power supply is cut off
The NC contact does not open when the power supply is cut off whether the inverter is operating or ceased.When the input side power supply is cut off, the DC... More Details >>
- No:21958
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-S500
-
Many geared motors cannot continuously operate at low speed (for example, slower than 6 Hz) due to grease viscosity.If the motor you are using is of this typ... More Details >>
- No:22028
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A024
561-570 of Total 1292