Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>
- No:21776
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Difference from general-purpose inverter
In general, both are inverters using the same control method, however, the inverter speed controller limits functions compared with the general-purpose inver... More Details >>
- No:21582
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , SC-A
-
Can I use a motor of which capacity is larger than the inverter capacity?
Even when the actual load (torque) is half of the motor capacity, the current output from the inverter to the motor is not reduced to the half. Therefore, it... More Details >>
- No:21442
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>
- No:21428
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
We recommend the "YM206RI 1 mA" analog ammeter. More Details >>
- No:21402
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
-
Operation of the motor with a brake
For the general-purpose inverter, the motor stop cannot be detected accurately because the actual motor speed from a motor is not input. In general, the RUN ... More Details >>
- No:21375
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Up to three plug-in options can be mounted. More Details >>
- No:21093
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , Plug-in Options , FREQROL-F800
-
Because the internal reset processing is performed when the power supply is turned OFF, the fault state cannot be held. The details of the faults are saved i... More Details >>
- No:20942
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options
-
Instantaneous power failure of facilities
1. If the start signal is present when the power and communication restore, the inverter starts operation. 2. Similarly to the above, if the start signal is ... More Details >>
- No:22093
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
I want to display the speed on an analog meter.
As the inverter does not display the speed in m/min, let us explain using the speed display in r/min. In this case, set Pr.52 to "6" (operation panel display... More Details >>
- No:21944
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500