FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
There is a priority between the setting dial and multi-speed settings.Since the multi-speed setting is given a higher priority, the setting by the setting di... More Details >>
- No:21702
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>
- No:21776
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>
- No:21827
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
The terminal MRS assignment parameter is Pr.183. Set Pr.183 to "4" (AU). (This setting is for the E700.) More Details >>
- No:21850
- Release Date:2018/08/22 16:29
- Category: FREQROL-E700
-
You can do so by setting Pr.339 (Communication speed command source) = 1 (external). More Details >>
- No:21881
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>
- No:21899
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
EMC compliant filter terminal cover
The SF1258 has the terminal cover.Although the SF1259 to SF1263 do not have the terminal covers and their terminals are bare, rubber tubes to cover them are ... More Details >>
- No:21956
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
When controlling motor with brake by inverter
Use the RUN signal to turn ON and OFF the brake.Using the MRS (output shutoff) signal to turn ON the brake shuts off the inverter's output and reduces influe... More Details >>
- No:21960
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Can I replace the cooling fan alone?
The fan of the FR-A024 cannot be replaced by the customer. Mitsubishi Electric System & Service will replace it, so contact us to order it. More Details >>
- No:22001
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A024
-
Built-in regenerative resistor
For both the 200 V and 400 V classes have the built-in regenerative resistor for 0.4 K to 7.5 K.The permissible power is as follows:Capacity: Short-time perm... More Details >>
- No:22021
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
591-600 of Total 1292