FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Safety stop function of the FR-D700/FR-E700
It is recommended to install the magnetic contactor on the input side of the inverter for safety. The category 3 can be satisfied without installing it. More Details >>
- No:20837
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700
-
It is possible when Pr.23 = 0 (Current limit at regenerative driving). More Details >>
- No:20826
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
Not required. Select it according to the capacity of the vector motor used. More Details >>
- No:20804
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
The phase detection terminal has been provided with units produced since December 1999. You can identify these units with the serial number "N9Z○○○○○○" or la... More Details >>
- No:22090
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Pulse train output of terminal FM
Under Advanced magnetic flux vector control, the output frequency varies due to slip compensation. This may cause the output frequency monitor value to chang... More Details >>
- No:22054
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
The inverter's output voltage is controlled by switching DC voltage and has a pulse voltage waveform.(It is not a clean sine wave.)Therefore, it cannot be me... More Details >>
- No:22029
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
1. The 100% braking torque means the 100% motor rated torque. Do not consider the continuous regenerative driving based on the braking torque. Consider the r... More Details >>
- No:22023
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Imbalanced input side power supply
1. Power supply voltage phase imbalance toleranceMitsubishi inverter's input power supply voltage phase imbalance tolerance is ±3%.If the phase imbalance exc... More Details >>
- No:21987
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Operation of automatic restart after instantaneous power failure
1. No operation log is recorded.2. No. However, you can create a state indicating that automatic restart after instantaneous power failure is in progress by ... More Details >>
- No:21948
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>
- No:21845
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
591-600 of Total 1292