If "1" is not shown on the frequency monitor, some of the parameters necessary for auto tuning may not be set correctly.Set rated motor current of Pr.81 (Num... More Details >>
- No:21751
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
No problem.The inverter converts AC power into DC power and then into AC (PWM) power output again. Therefore, it is not influenced by the power supply phase ... More Details >>
- No:21925
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
I want to synchronize the Z200 and E500.
If you are using analog voltage commands, connect the voltage inputs to the FR-E500 and FR-Z200 in parallel to equalize inputs to both units and speeds are s... More Details >>
- No:21929
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500 , FREQROL-Z200
-
You can set both the BCD code and binary code inputs within the range from 0 to 400 Hz.You can set the bias and gain in 0.01 Hz units.For BCD input, when the... More Details >>
- No:21945
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500
-
When controlling motor with brake by inverter
Use the RUN signal to turn ON and OFF the brake.Using the MRS (output shutoff) signal to turn ON the brake shuts off the inverter's output and reduces influe... More Details >>
- No:21960
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Fault output terminal load pattern
The fault output terminals A and C, and B and C of the power regeneration converter FR-RC are not capable of a micro load of 5 VDC±5%, 10 mA. The minimum loa... More Details >>
- No:21966
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Inverter 200 V input and 400 V output
We do not have an inverter that directly takes 200 V input and generates 440 V output. Therefore, as you mention, use a 400 V class inverter by boosting the ... More Details >>
- No:21971
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
When the command frequency is 0 Hz, the inverter does not generate output and the voltage is 0 V. More Details >>
- No:22011
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
When all of the multi-speed input signals are turned OFF during external operation, the output frequency conforms to the external analog frequency command (i... More Details >>
- No:22012
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Inverter's heat generation quantity
The heat generation quantity while the inverter is outputting the rated current is as follows:1. FR-A520-3.7K: 230 W2. FR-A520-7.5K: 420WThe heat generation ... More Details >>