For the V/F control and Advanced magnetic flux vector control, the FR-A800 stops only by Pr.1103 Deceleration time at emergency stop. Pr.815 is not affected. More Details >>
- No:20860
- Release Date:2018/08/22 16:24
- Category: FREQROL-A800
-
Yes, they can. More Details >>
- No:20856
- Release Date:2018/08/22 16:24
- Category: FREQROL-A800
-
Setting value of Pr.72 (FR-B, B3 (A800 base))
For the normal type (FR-B3) is 2 KHz. For the low-noise type (FR-B3-N), 14.5 KHz. More Details >>
- No:20828
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-B
-
Combination of the FR-F800 and MM-EFS
Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>
- No:20820
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-F800
-
The power factor is 0.99 or more (at rated load). More Details >>
- No:20803
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
- Both 200 V and 400 V can be used only with the capacity 22 kW or higher. - The rated current (capacity) is derated. (For the detail, refer to the Instructi... More Details >>
- No:20802
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
Square wave input is not recommended since it can cause failures (for example, damage the diode bridge). More Details >>
- No:22106
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-E500
-
Influence on external measurement device
It is considered that malfunction of the measurement device is due to noise. Check the noise propagation route since the countermeasure depends on it. Some c... More Details >>
- No:22100
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Others
-
If the MC on the input side is shut off using the fault output of the FR-E500, the inverter's fault records are left in the faults history. More Details >>
- No:22096
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Can I set the FR-F series parameters?
The FREQROL-F500 series has been already supported by the setup software released since February 2000. More Details >>
- No:22068
- Release Date:2018/08/22 16:30
- Category: Engineering Software