FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>
- No:21192
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>
- No:21191
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>
- No:21189
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Power is supplied only to the control power supply, and thus this enables communication, parameter setting through the operation panel or an USB memory devic... More Details >>
- No:21097
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , FREQROL-F800
-
Operation at external operation/stop
It is recommended to turn OFF the start signals (STF and STR) when stopping the inverter.In this case, it is not probable that the motor rotates due to a cal... More Details >>
- No:22102
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-E500
-
Calculation of inverter acceleration and deceleration time
Refer to the Technical Sheet No.23 (Capacity Selection and Continuous Operation) for reference for selection. Optional capacity selection software is also pr... More Details >>
- No:22097
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
How can I have the motor coast to stop?
You can use the following two methods:1. Turn ON MRS at the same time when STF turns OFF.2. Set Pr.10 = 60 Hz, Pr.11 = 0 sec, and Pr.12 = 0% (when the invert... More Details >>
- No:21967
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
You can start/stop operation, set the frequency, read/write parameters, and monitor the inverter via CC-Link communication. More Details >>
- No:21901
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>
- No:21892
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
681-690 of Total 1306