FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>
- No:20905
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>
- No:20884
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
FR-A800 "Parameter for the communication setting"
These parameters are used for the communication compatible with the communication protocol of the Ethernet IP of the HMS optional circuit board (A8NEIP_2P). More Details >>
- No:20824
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800
-
Installation clearance of inverters
Keep 1 cm or more of clearance for 3.7 K or smaller, and 5 cm or more for 5.5 K or larger.If the clearance is too small, the cooling effect is lowered. Secur... More Details >>
- No:22046
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Keep Y100D turned ON if you are changing the frequency continuously. More Details >>
- No:21883
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
When offline auto tuning ends normally, the setting of this parameter changes to "3".This means that auto tuning completed normally.If the setting value is "... More Details >>
- No:21748
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
Although you specify the FR-V200 and others as the inverter models, CC-Link is currently supported by the FR-A500 and FR-E500. The FR-V200E does not support ... More Details >>
- No:21499
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
The following causes are probable for persistent Err. display: 1. The terminals RES and SD are always short-circuited. 2. Operation panel contact or operatio... More Details >>
- No:21412
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Countermeasures when input power supply is turned off upon equipment fault
1. When the inverter power supply is turned OFF, the inverter is disconnected from the CC-Link network. However, since the CC-Link master station has the aut... More Details >>
- No:21390
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
It can be performed by setting Pr.292 (Automatic acceleration/deceleration) to "8" and Pr.279 (Brake opening current) to 0%. More Details >>
- No:21186
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700