When the PG24 terminal and the PG terminal are shorted, 24 VDC power for the encoder can be supplied from the PG24 terminal. More Details >>
- No:20954
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Plug-in Options
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
The high speed command (multi-speed command) is prioritized over the frequency setting potentiometer. It is OK if these are both input simultaneously. When t... More Details >>
- No:21424
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-U100
-
Yes. "OL" is displayed under speed control whenever the torque limit is reached without regard to the rated torque. More Details >>
- No:21448
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-V200
-
The internal processing speed is not published. The analog input specifications are as follows: FR-A500???1/4000FR-E500???1/1000MR-H???1/4000 More Details >>
- No:21550
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
By adopting Mitsubishi proprietary digital vector control, high torque (150% 60 sec) and fast-response (speed loop 200 rad/sec) are achieved. The speed contr... More Details >>
- No:21664
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-V200
-
Installation method of AM-5 terminal ammeter
The AM-5 output is 0 to 10 VDC voltage output.Therefore, you need to install a voltmeter.Also, since the inverter output current is displayed, the scale of t... More Details >>
- No:22016
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-F500
-
Installation clearance of inverters
Keep 1 cm or more of clearance for 3.7 K or smaller, and 5 cm or more for 5.5 K or larger.If the clearance is too small, the cooling effect is lowered. Secur... More Details >>
- No:22046
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
The power factor is 0.99 or more (at rated load). More Details >>
- No:20803
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
No, it cannot. Use the FR-HC2 dedicated reactor and outside box. More Details >>
- No:20807
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options