The motor-generated torque elements have the following relationship:Torque T = K I V/FK: ConstantI: CurrentV: VoltageF: FrequencyThe inverter regularly perfo... More Details >>
- No:21952
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
To set the frequency via CC-Link communication, the NET mode should be selected. The new parameter setting is applied after powering OFF and then ON the inve... More Details >>
- No:21763
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>
- No:21722
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
The following is the amount of heat generated for each capacity:0.1K: 14W 0.2K: 20W 0.4K: 32W 0.75K: 50W1.5K: 80W 2.2K: 100W 3.7K: 160W 5.5K: 290W7.5K:... More Details >>
- No:21706
- Release Date:2018/08/22 16:29
- Category: FREQROL-E700
-
Manufacturing of 6P dedicated motor
We cannot manufacture a 6P by SF-VR dedicated motor. Use a motor with 6P encoder. More Details >>
- No:21646
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-V200
-
Difference in purpose from FR-A200 series
Reference of proper use of each series is as follows: - A024: When balance between size, performance, and cost is important. - A200: When system configuratio... More Details >>
- No:21610
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A024
-
Regenerative driving capability
Continuous 100% regenerative braking torque is available for the rated capacity of the high power factor converter. (The same braking ability of the FR-A201 ... More Details >>
- No:21563
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Options
-
This error is displayed when the inverter and operation panel FR-PU04 cannot communicate with each other correctly or the reset signal remains ON. Therefore,... More Details >>
- No:21546
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
It is considered that communication settings between the inverter and personal computer do not match. Check if settings such as communication rate and stop b... More Details >>
- No:21431
- Release Date:2018/08/22 16:27
- Category: Engineering Software
-
No, it does not run. "Err" is displayed when it is operated. Always input the same voltage (400 V) to the main power supply and control power supply. More Details >>
- No:21179
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P