If you connect two frequency setting potentiometers to the terminals 5 and 10, the permissible current of 10 mA is exceeded, and you need to install 2 KΩ res... More Details >>
- No:21494
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Which is the recommended digital counter?
We recommend the following digital counter: (Connect it between the terminals FM and SD.) Manufacturer: KOYO ELECTRONICS INDUSTRIES CO., LTD.Model: TC-41 More Details >>
- No:21469
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Others , FREQROL-A500
-
Installing magnetic contactor on input side of inverter
Basically, there is no difference between the A200 and A500. For safer use, from the A500, it is recommended to completely shut off the power supply by turni... More Details >>
- No:21466
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
You can use an inverter for fan and pump with the compressor, but it is not recommended for an application that the motor load rapidly increases. More Details >>
- No:21443
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A100
-
The FM output is the 1440 Hz, 1 mA pulse train output at full scale. You can input to the programmable controller if it has a pulse train input. A68AD does n... More Details >>
- No:21439
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
We recommend the "YM206RI 1 mA" analog ammeter. More Details >>
- No:21402
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
-
Providing thermal protection is better for your safety. When the brake transistor explodes, the brake transistor alarm (E.BE) is output. Consider a counterme... More Details >>
- No:21397
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
Is the number of writing times of the parameter memory limited?
1. The limit of the parameter writing is 100,000 times. 2. Parameter error occurs. Since the data in the ROM may be broken, the inverter may become unavailab... More Details >>
- No:21385
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Check the setting value of Pr.73. Or check Pr.C4 (Terminal 2 frequency setting gain) for the percentage of the voltage that is actually applied. For the FR-E... More Details >>
- No:21356
- Release Date:2018/08/22 16:27
- Category: FREQROL-E700
-
The signals MRS and CS are required when the automatic bypass sequence enabled. More Details >>
- No:21187
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P