You can change the full-scale value by changing Pr.55 (Frequency monitor reference). The initial setting is 60 Hz. More Details >>
- No:21672
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Fault output terminal A, B, and C
Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>
- No:21324
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>
- No:21843
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
External installationRated current
Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>
- No:21817
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>
- No:21909
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
This subroutine is to check the data link status and needs to be executed only once at the start of the program. More Details >>
- No:21767
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
10 VDC voltage from terminal 10
Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>
- No:21727
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>
- No:21685
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
When using the setting dial to set the frequency, turn the dial and display the frequency. Then, press the "SET" key while the desired value flickers.The fre... More Details >>
- No:21848
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ