No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>
- No:20878
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
The direct connection with the inverter like the standard model, and the connection via the GOT and relay station (programmable controller) are available. On... More Details >>
- No:20879
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>
- No:20881
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>
- No:20882
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
When it is required to keep the safety of the inverter and the system against unauthorized access from external devices via the network, take countermeasures... More Details >>
- No:20883
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>
- No:20899
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Carrier frequency automatic reducing function
The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>
- No:20903
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>
- No:20904
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Residual voltage at the output shutoff
The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>
- No:20906
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Vector control: The SM1217 turns ON when the motor rotates even if no forward rotation command is send. Other than vector control: The SM1217 turn ON by forw... More Details >>
- No:20907