No, it cannot be normally closed contact. When the electronic bypass function is used, the setting of Pr.17 is disabled. More Details >>
- No:21193
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
CC-Link monitor and parameter setting
1. Since you can monitor the output frequency independently, you do not need to switch monitoring by the monitor commands. Assign the remote register RWr0 to... More Details >>
- No:21418
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
The high speed command (multi-speed command) is prioritized over the frequency setting potentiometer. It is OK if these are both input simultaneously. When t... More Details >>
- No:21424
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-U100
-
Number of inverters that can be connected to a 20 A branch circuit breaker
The basic idea is the same, but the total capacity should be 3.7 kW. (The maximum capacity is also 3.7K.) More Details >>
- No:21508
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-A024
-
Acquisition of pressure-resistant explosion-proof certification
The test institutes assigned by the Minister of Health, Labour and Welfare (National Institute of Occupational Safety and Health and Technology Institution o... More Details >>
- No:21510
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-B
-
If all inverters are in regenerative operation, the regenerative power is regenerated to the power supply. If one of the inverters is power driving, the rege... More Details >>
- No:21564
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Options
-
FR-E700, D700, and F700PJ do not have the terminal CS and you can only control automatic restart by setting Pr.57 (Restart coasting time). More Details >>
- No:21707
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21730
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
When offline auto tuning ends normally, the setting of this parameter changes to "3".This means that auto tuning completed normally.If the setting value is "... More Details >>
- No:21748
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
Set it to "13" (Constant-torque). More Details >>