FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
For the 200 V type, the leakage current at the delta connection is 5 mA. For the 400 V type, it is 10 mA. More Details >>
- No:20835
- Release Date:2018/08/22 16:24
- Category: Options
-
Yes. More Details >>
- No:20810
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Others
-
Refer to the following points.For fan pump -> Square torqueFor general-purpose machine (for example, transport, elevation) -> Constant-torque type More Details >>
- No:22048
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
As an example, you can use an inverter to feed the cord at the constant speed under dancer control using a combination of the deviation detector and deviatio... More Details >>
- No:22047
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
1. You can implement stop-on-contact.2. When implementing stop-on-contact, use the inverter to decelerate the motors to reduce the impact upon stop-on-contac... More Details >>
- No:22041
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Be sure to use the FR-E5P to mount the operation panel.This is because the board is bare on the back of the operation panel and a dedicated connector is requ... More Details >>
- No:22030
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Changing main speed at analog signal input
To change the running frequency while the frequency command is input to the terminal 2, adjust the parameters in the following steps:1. Change Pr.77 to "2".2... More Details >>
- No:22025
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Since the FR-A540-0.75K has a brake transistor for resistor regenerative driving inside the inverter, you do not need to use BU. Just remove the jumper from ... More Details >>
- No:21992
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Current input switching operation
With your setting, since Pr.60 assigns the OH function to the terminal PL, and terminals RL and SD are open, an external protection error occurs. (It does no... More Details >>
- No:21975
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-S500
-
Fault output terminal load pattern
The fault output terminals A and C, and B and C of the power regeneration converter FR-RC are not capable of a micro load of 5 VDC±5%, 10 mA. The minimum loa... More Details >>
- No:21966
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options