FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Input terminal function selection of multi-function series
You can use the input terminals X1 to X3 for an input terminal function such as 7-speed operation (high, middle, and low speed), output stop during motor ope... More Details >>
- No:21601
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-U100
-
FR-E700, D700, and F700PJ do not have the terminal CS and you can only control automatic restart by setting Pr.57 (Restart coasting time). More Details >>
- No:21707
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21730
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Turn ON the monitor command RYC. More Details >>
- No:21826
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Check if the master station uses CC-Link Version 1 and the FR-A7NC uses CC-Link Version 2. More Details >>
- No:21831
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
FR-PA02 built-in potentiometer
Change Pr.146 (Built-in potentiometer switching) to "0" (built-in frequency setting potentiometer). More Details >>
- No:21862
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Up to 42 units can be connected. (When only inverters are connected) More Details >>
- No:21873
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Output phase loss protection error
- How to find out lost phaseMeasure the three-phase current when the error has occurred.The phase with a small (or no) phase current is lost.- Possibility of... More Details >>
- No:21969
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
If the parameters related to the output voltage are not changed from the initial setting, it is unlikely that the output current at 55 Hz and 60 Hz is double... More Details >>
- No:21983
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-S500
-
Since the FR-A540-0.75K has a brake transistor for resistor regenerative driving inside the inverter, you do not need to use BU. Just remove the jumper from ... More Details >>
- No:21992
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
871-880 of Total 1292