FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Current increase at motor stop
If the current increases when the motor stops under V/F control (at low speed under a light load), the motor is considered to be in the overexcitation state.... More Details >>
- No:21997
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Frequency misalignment at current input
It seems that calibration of the current input is slightly incorrect.By using Pr.904 (Frequency setting current bias) and Pr.905 (Gain), you can calibrate th... More Details >>
- No:22014
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Amount of heat generated by the FR-V500L
It is the same as the one by the inverter whose capacity is one-rank higher than the FR-A500L series. More Details >>
- No:20854
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL
-
Yes, the changed parameters can be displayed with the verification function. Select Parameter list → Verification → Initial value. More Details >>
- No:20918
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
Yes, it is preferred. The accuracy becomes worse when the gap between the setting value and actual value increases. More Details >>
- No:20932
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
It is the length from the support of the rope to the center of gravity of the swinging. More Details >>
- No:20934
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
They are cleared as well. More Details >>
- No:21207
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
LED blinking under encoder feedback control
The Z-phase signal may be connected to the A-phase or B-phase incorrectly. Check the wiring. More Details >>
- No:21220
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Priority of multi-speed setting and frequency setting signals
For frequency setting, multi-speed setting is prioritized over current input. Therefore, when the multi-speed signal is input, the inverter switch to multi-s... More Details >>
- No:21400
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
Operation at base frequency or higher
The output frequency is 55 Hz. (For V/F control)When the base frequency is set to 50 Hz, frequencies over 50 Hz is the constant output range.Note that the ma... More Details >>
- No:21923
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
81-90 of Total 1292