For countermeasures against the open/close surge of the MC (magnetic contactor). Insert a diode not to apply 27 VDC or more to the open collector terminal of... More Details >>
- No:21188
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>
- No:21190
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
The parameter file (extension: pr3) can be imported. The system file (extension: mel) cannot be imported. More Details >>
- No:21194
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Refer to the inverter capacity. More Details >>
- No:21200
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
When the brake sequence function is enabled, the RT signal is disabled and the stop-on-contact control cannot be performed. More Details >>
- No:21209
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Overshooting of the speed due to the acceleration/deceleration may be the cause. Overshooting is more likely to occur when the load inertia is too high. As a... More Details >>
- No:21216
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
There is no setting to disable it, but setting a high torque limit level such as 400 % can disable the limit. More Details >>
- No:21217
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
LED blinking under encoder feedback control
The following may be the cause. - No encoder power supply. - The setting of Pr.359 (Encoder rotation direction) is reversed. - The signal from the encoder is... More Details >>
- No:21219
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Inverter installation when using the FR-A7NCE
Normally, the required space for A700 3.7K or lower is 1 cm. However, when using CC-Link IE, it needs to be separated for 5 cm or more to pass the cable. More Details >>
- No:21227
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Remote register when instruction code execution request is issued at CC-Link communication
The value "0" is stored. More Details >>
- No:21234
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL