FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Operation panel extension cable
Yes, you can use the 10BASE-T cable (straight) with the E500. More Details >>
- No:22085
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
With the FREQROL-U100 series, pressing and holding the [SET] switches to the current monitor. More Details >>
- No:22073
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-U100
-
The estimated lives of the parts of the FREQROL-E500 are as follows: Cooling fan at surrounding air temperature of 35 deg C???30,000 hrsPower supply smoothin... More Details >>
- No:22071
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
All parameters returned to initial values
The parameters of the A500 series are stored in the EEPROM.The reason why all parameters returned to the initial values is considered that you may have opera... More Details >>
- No:22066
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
To supply power via R1 and S1, 60 VA or higher is necessary for 22K or lower and 80 VA or higher is necessary for 30K to 55K.Note that the rush current of ap... More Details >>
- No:22043
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Fault contact when connecting separate power supply for each control circuit
Since the inverter's fault contact is an NC contact, it does not open unless a fault occurs.Therefore, when the control power supply (and main circuit power ... More Details >>
- No:22035
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Using shielded wires for frequency meter connection
Connect the shield to the terminal SD. More Details >>
- No:22034
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Be sure to use the FR-E5P to mount the operation panel.This is because the board is bare on the back of the operation panel and a dedicated connector is requ... More Details >>
- No:22030
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Inverter selection when driving multiple motors
When driving multiple motors with a single inverter, determine the inverter capacity in one of the following two methods:1. When driving multiple motors conn... More Details >>
- No:22007
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Surge voltage of 400 V inverter
1. Since the voltage resistance of the standard motor is not improved, it is recommended to use an "insulation-enhanced motor".If you are using an insulation... More Details >>
- No:21957
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Others
901-910 of Total 1292