When both "Hz" and "A" are turned off, the output voltage monitor is active.The display indicates that the output voltage is 19.5 V. More Details >>
- No:21782
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Output frequency monitor value
When running the inverter after auto tuning, the frequency setting value is increased by the amount of the motor slippage, resulting in a higher monitor valu... More Details >>
- No:21781
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
If you try to change a parameter in other than the PU operation mode, the mode specification error "Er4" may occur.Set the parameters in the PU operation mod... More Details >>
- No:21778
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>
- No:21775
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Display unit of operation panel
Set the rotations per minute that is obtained while operating at the frequency set with Pr.505 (Speed setting reference) to Pr.37 (Speed display).For example... More Details >>
- No:21774
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700P , FREQROL-F700PJ
-
To use the terminal as voltage input, you need to:- Set Pr.267 (Terminal 4 input selection).- Set the voltage/current input switch on the inverter board.- Se... More Details >>
- No:21771
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>
- No:21765
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Press the "SET" key once while the output frequency is monitored.The unit indicator LED changes from "Hz" to "A" and the monitor display changes to the current. More Details >>
- No:21764
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
1. Press the PU/EXT key on the operation panel FR-PA07 to choose the PU operation mode. Set Pr.161 (Frequency setting/key lock operation selection) to "1" an... More Details >>
- No:21761
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
After setting Pr.340 to "10", you need to power OFF then ON the inverter to make the new setting enabled because you are setting the operation upon power-on.... More Details >>