Operation stop, frequency setting
Set Pr.79 (Operation mode) to "1" (PU operation mode). More Details >>
- No:21819
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Yes. However, write the setting data to the RAM of the inverter.Set RWw1 in the setting value and turn ON the frequency setting command RYD.To continuously s... More Details >>
- No:21825
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
FR-PA02 built-in potentiometer
Change Pr.146 (Built-in potentiometer switching) to "0" (built-in frequency setting potentiometer). More Details >>
- No:21862
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
You can start/stop operation, set the frequency, read/write parameters, and monitor the inverter via CC-Link communication. More Details >>
- No:21901
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>
- No:21911
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
You can use it for inverter operation, but the running speed of the inverter does not change linearly with regard to turn of the frequency setting potentiome... More Details >>
- No:21912
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
You can set both the BCD code and binary code inputs within the range from 0 to 400 Hz.You can set the bias and gain in 0.01 Hz units.For BCD input, when the... More Details >>
- No:21945
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500
-
Fault contact state when input side power supply is cut off
The NC contact does not open when the power supply is cut off whether the inverter is operating or ceased.When the input side power supply is cut off, the DC... More Details >>
- No:21958
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-S500
-
AC reactor and line noise filter wiring
Basically, either is OK.Both orders are electrically identical, but "1" is recommended since it is preferable to place the line noise filter close to the inv... More Details >>
- No:21964
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Set the parameters below. For other parameters, keep the initial settings.1. Set Pr.122 (Communication check time interval) to other than "0". ("9999" is OK.... More Details >>