FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Proper use of AC reactor and DC reactor
1. ACL has the input power factor of approximately 90% and DCL has the input power factor of approximately 95%. Therefore, DCL has a higher input power facto... More Details >>
- No:21949
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Refer to the following points.For fan pump -> Square torqueFor general-purpose machine (for example, transport, elevation) -> Constant-torque type More Details >>
- No:22048
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Frequency does not rise with blower
Our suggestion is to adjust the following parameters:1. Set Pr.14 = 0. If the V/F pattern for variable-torque load (Pr.14 = 1) is used, the current may incre... More Details >>
- No:22060
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-F500
-
Insulation level of the MM-EFS
F class (155 deg C) More Details >>
- No:20809
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Others
-
The ON level is the power supply voltage -3 V or higher and the OFF level is 3 V or lower. More Details >>
- No:21002
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , Plug-in Options
-
A radio noise filter can be used with a built-in filter. More Details >>
- No:21113
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , Options , FREQROL-F800
-
It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>
- No:21180
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>
- No:21251
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
By setting Pr.160 (User group read selection ("Extended function display selection" for D700)) to "0", all the parameters can be read. More Details >>
- No:21262
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
941-950 of Total 1292