For the set frequency 60 Hz, ±6 Hz is applied and thus the up to frequency signal is output between 54 Hz and 66 Hz. During acceleration/deceleration to the ... More Details >>
- No:21348
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Encoder feedback speed accuracy
The speed variation rate is as follows: - Encoder feedback control: ±0.2% - Vector control: ±0.02% (mentioned in FR-A5AP Instruction Manual) More Details >>
- No:21422
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>
- No:21892
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Acceleration/deceleration time
You cannot set and/or enable the acceleration time and deceleration time individually. More Details >>
- No:21938
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , SC-A
-
The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>
- No:20882
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
It is 1 s interval. More Details >>
- No:21055
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , FREQROL-F800
-
No. (Using the copy function causes an error.) Use the FR-DU08 when performing the copy function of the operation panel. More Details >>
- No:21118
- Release Date:2018/08/22 16:26
- Category: FREQROL-A800 , Options , FREQROL-F800
-
Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>
- No:21245
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Resetting inverter after restoring from power failure
When the programmable controller power is turned OFF while the inverter is in the PLC link operation mode, a communication error occurs and the inverter trip... More Details >>
- No:21417
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500