Can I connect it to high power factor converter?
It can be connected to an inverter that supports the high power factor converter FR-HC. (It cannot be connected to conventional inverters.) How to identify i... More Details >>
- No:21602
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A024
-
Can a single potentiometer operate two speed controller?
A single potentiometer cannot operate two speed controller. Reason: Since the control circuit and main circuit of the SC-A speed controller are not insulated... More Details >>
- No:21578
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , SC-A
-
The high power factor converter itself is almost same size as general-purpose inverter with the same capacity (FREQROL-A200 series), however, an additional s... More Details >>
- No:21571
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Options
-
Amount of heat generated by inverter
Refer to Section 2-45 and 2-46 of the FR-A series technical material. More Details >>
- No:21554
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A200
-
Faults history upon power failure
When an instantaneous power failure of 100 msec or longer occurs, the inverter is reset* and it is not recognized as a fault. Since it is not recognized as a... More Details >>
- No:21551
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Installing contactor on input side
It is not recommended to install a contactor on the input side and connect the auxiliary contact to the terminal STF of the inverter for the following reason... More Details >>
- No:21533
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL
-
Number of inverters that can be connected to a 20 A branch circuit breaker
The basic idea is the same, but the total capacity should be 3.7 kW. (The maximum capacity is also 3.7K.) More Details >>
- No:21508
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-A024
-
Motor heat generation at low-speed operation
When using the FR-A540-3.7K in Advanced magnetic flux vector control, operating the motor continuously under the 100% torque at up to 3 Hz does not cause a h... More Details >>
- No:21496
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Simple torque control using stall prevention function
Basically, torque control cannot be performed. Instead, control speed to adjust the winding torque. It is possible to use the current limit function to preve... More Details >>
- No:21493
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Connecting voltmeter to terminal AM
You can connect them in parallel. Connect the voltmeters in parallel, paying attention to the following: - The output current should not exceed the permissib... More Details >>
- No:21464
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL