  • Power supply capacity

    Since the input power factor is improved to approximately 1, the power supply capacity can be reduced to 2/3 to 3/4 of an inverter without a power factor imp... More Details >>

    • No:21556
    • Release Date:2018/08/22 16:28
  • Connection of options

    1. As the reactor (FR-HCL) is connected when connecting the FR-HC, do not connect the FR-BAL. 2. The noise filter can be connected to the input side of the F... More Details >>

    • No:22101
    • Release Date:2018/08/22 16:30
  • Connection of the FR-HAL

    Yes. More Details >>

    • No:20985
    • Release Date:2018/08/22 16:25
  • Brake unit selection

    1. The BU brake unit does not have the fault output.Multiple BU brake units can be connected in parallel.2. Power supply voltage 480 V- What resistance value... More Details >>

    • No:21930
    • Release Date:2018/08/22 16:30
  • FR-XC

    The power factor is 0.99 or more (at rated load). More Details >>

    • No:20803
    • Release Date:2018/08/22 16:24
  • FR-HC2

    A current fluctuation may result in abnormal noise from the peripheral device or the flickering fluorescent light. More Details >>

    • No:21155
    • Release Date:2018/08/22 16:26
  • Regenerative driving capability

    Continuous 100% regenerative braking torque is available for the rated capacity of the high power factor converter. (The same braking ability of the FR-A201 ... More Details >>

    • No:21563
    • Release Date:2018/08/22 16:28
  • Harmonic suppression guidelines for power supply

    Since the high power factor converter uses the self-excitation three-phase bridge (voltage type PWM control) circuit configuration (type), the conversion coe... More Details >>

    • No:21572
    • Release Date:2018/08/22 16:28
  • System configuration

    The whole system consists of the power supply, molded case circuit breaker, high power factor converter, inverter, and motor. The high power factor converter... More Details >>

    • No:21575
    • Release Date:2018/08/22 16:28
  • FR-XC

    - Both 200 V and 400 V can be used only with the capacity 22 kW or higher. - The rated current (capacity) is derated. (For the detail, refer to the Instructi... More Details >>

    • No:20802
    • Release Date:2018/08/22 16:24