  • Using both types of power factor improving reactors

    Yes.By using both types of reactors together, you can reduce the outgoing harmonic current.For examples of harmonics reduction, refer to the value in the har... More Details >>

    • No:21995
    • Release Date:2018/08/22 16:30
  • Installation of a reactor

    The answers are as follows:- Effect of reactorAttaching a reactor improves the power factor and suppresses harmonics.The AC reactor improves the power factor... More Details >>

    • No:22092
    • Release Date:2018/08/22 16:30
  • MT-BU5

    No, the MT-BU5 is not available Use the FR-BU2 instead. More Details >>

    • No:21076
    • Release Date:2018/08/22 16:25
  • Fault output terminal load pattern

    The fault output terminals A and C, and B and C of the power regeneration converter FR-RC are not capable of a micro load of 5 VDC±5%, 10 mA. The minimum loa... More Details >>

    • No:21966
    • Release Date:2018/08/22 16:30
  • FR-A842

    The inrush current limit circuit is not built in the FR-A842 (inverter unit). It is built in the FR-CC2 (converter unit), which is combined with the FR-A842.... More Details >>

    • No:21059
    • Release Date:2018/08/22 16:25
  • FR-A8TAT

    Yes, it does. (There are some restrictions. More Details >>

    • No:21082
    • Release Date:2018/08/22 16:25
  • DC reactor

    If using an inverter with capacity of 75K or higher, or motor with capacity of 75 kW or higher, always select and install the inverter based on the capacity ... More Details >>

    • No:21112
    • Release Date:2018/08/22 16:25
  • FR-A5CN

    When the heat sink is outside, since the heat sink and fan are not waterproof, you need to enclose them so that they are not exposed to the spray of water. More Details >>

    • No:21435
    • Release Date:2018/08/22 16:27
  • Synchronous operation of two motors

    When synchronously operating two motors, you need to detect speed from both motors. Each inverter is controlled based on this speed detection signal. As an e... More Details >>

    • No:21540
    • Release Date:2018/08/22 16:28
  • Combination of the FR-F800 and FR-A8TAT

    Yes, it can. For the capacity of 37K or more, use the included bracket for installation. More Details >>

    • No:20841
    • Release Date:2018/08/22 16:24