  • EMC compliant filter terminal cover

    The SF1258 has the terminal cover.Although the SF1259 to SF1263 do not have the terminal covers and their terminals are bare, rubber tubes to cover them are ... More Details >>

    • No:21956
    • Release Date:2018/08/22 16:30
  • Inverter selection when multiple inverters are to be connected

    Be sure to use a high power factor converter with the capacity higher than the total capacity of the inverters connected. (Note: One or more of the inverters... More Details >>

    • No:21565
    • Release Date:2018/08/22 16:28
  • Influence on noise level

    By using the reactors 1 and 2 as well as the outside box supplied with the high power factor converter, while the noise may increase or decrease depending th... More Details >>

    • No:21559
    • Release Date:2018/08/22 16:28
  • FR-CV

    At power-ON, the signal turns ON for a moment to perform a converter initial reset. More Details >>

    • No:21156
    • Release Date:2018/08/22 16:26
  • FR-HC2

    It controls the charging current immediately after the power is ON. (as a resistor for charging current limit circuit) More Details >>

    • No:21150
    • Release Date:2018/08/22 16:26
  • FR-HC2

    The power of MC1 is supplied from the terminals across R2 and S2 of the outside box. Either phase of R2 or S2 may be lost. More Details >>

    • No:21146
    • Release Date:2018/08/22 16:26
  • FR-HC2

    Three phases are measured with the CT. The accuracy is ±10 % which is same as the inverter output current. More Details >>

    • No:21145
    • Release Date:2018/08/22 16:26
  • FR-E700-SC

    Not available for the FR-E700-SC. For the 485 communication with the terminal block, use the standard FR-E700. More Details >>

    • No:21130
    • Release Date:2018/08/22 16:26
  • FR-HAL

    The UL94V-0 flammability standard is satisfied. More Details >>

    • No:20990
    • Release Date:2018/08/22 16:25
  • FR-ASF

    The FR-ASF may be damaged due to the surge voltage. More Details >>