  • Use of the FR-RC

    Yes. More Details >>

    • No:21062
    • Release Date:2018/08/22 16:25
  • Control terminal block

    It is available if the option FR-A8TAT (Control circuit terminal block intercompatibility attachment) is installed. (Some functions have restrictions. For th... More Details >>

    • No:21087
    • Release Date:2018/08/22 16:25
  • DC reactor

    It can be used since the specifications are the same. Note that the warranty period and expected lifespan for the A700/F700P are inherited. More Details >>

    • No:21092
    • Release Date:2018/08/22 16:25
  • Influence on noise level

    By using the reactors 1 and 2 as well as the outside box supplied with the high power factor converter, while the noise may increase or decrease depending th... More Details >>

    • No:21559
    • Release Date:2018/08/22 16:28
  • Combination with power factor improving reactor

    It cannot be combined with the power factor improving reactor. (Since the power factor is further improved by the high power factor converter, it is not requ... More Details >>

    • No:21560
    • Release Date:2018/08/22 16:28
  • Installation of a reactor

    The answers are as follows:- Effect of reactorAttaching a reactor improves the power factor and suppresses harmonics.The AC reactor improves the power factor... More Details >>

    • No:22092
    • Release Date:2018/08/22 16:30
  • TH3 terminal of the MT-BR5

    The resistor unit MT-BR5 manufactured in February 2016 or later has output terminal TH3 (NC contact) as a fault output terminal. More Details >>

    • No:20816
    • Release Date:2018/08/22 16:24
  • FR-HC2

    Perform the writing after turning ON the SOF, or after stopping the FR-HC2 by pressing the STOP button. Wire the RDY signal so that the inverter stops when t... More Details >>

    • No:20842
    • Release Date:2018/08/22 16:24
  • FR-BLF

    □□□□□□ Year Month (Control number) The last digit of the manufactured year is indicated as the Year, and the Month is indicated by (A → B → C... ⇒ January → ... More Details >>

    • No:20983
    • Release Date:2018/08/22 16:25
  • FR-LU08

    Approximately 2 years when the FR-LU08 is not energized and the real-time clock function is enabled. More Details >>

    • No:21084