  • FR-BSF-01

    □□□□□□ Year Month (Control number) The last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9, X (October), Y (Nove... More Details >>

    • No:20982
    • Release Date:2018/08/22 16:25
  • Connection of options

    1. As the reactor (FR-HCL) is connected when connecting the FR-HC, do not connect the FR-BAL. 2. The noise filter can be connected to the input side of the F... More Details >>

    • No:22101
    • Release Date:2018/08/22 16:30
  • Fault output terminal load pattern

    The fault output terminals A and C, and B and C of the power regeneration converter FR-RC are not capable of a micro load of 5 VDC±5%, 10 mA. The minimum loa... More Details >>

    • No:21966
    • Release Date:2018/08/22 16:30
  • Using a higher grade power factor improving reactor

    Using a reactor under a load lighter than the rated capacity slightly spoils its effect in improving the power factor.Therefore, you should use a reactor wit... More Details >>

    • No:21935
    • Release Date:2018/08/22 16:30
  • Output voltage

    The output voltage is approximately 300 VDC for the 200 V class and approximately 600 VDC for the 400 V class.  The output voltage fluctuates due to fluctuat... More Details >>

    • No:21561
    • Release Date:2018/08/22 16:28
  • Influence on leakage current

    Since the converter in the high power factor converter section performs PWM switching, the leakage current increases to the same level as the general-purpose... More Details >>

    • No:21558
    • Release Date:2018/08/22 16:28
  • Control terminal block

    It is available if the option FR-A8TAT (Control circuit terminal block intercompatibility attachment) is installed. (Some functions have restrictions. For th... More Details >>

    • No:21087
    • Release Date:2018/08/22 16:25
  • FR-A8TAT

    Yes, it does. (There are some restrictions. More Details >>

    • No:21082
    • Release Date:2018/08/22 16:25
  • Use of the FR-RC

    Yes. More Details >>

    • No:21062
    • Release Date:2018/08/22 16:25
  • Connection point of the line noise filter

    Connect the line noise filter between the inverter and EMC Directive compliant noise filter. More Details >>

    • No:20818
    • Release Date:2018/08/22 16:24