  • FR-BIF

    It is available. Insulate the raised wiring of T-phase. More Details >>

    • No:21177
    • Release Date:2018/08/22 16:26
  • Analog ammeter

    We recommend the "YM206RI 1 mA" analog ammeter. More Details >>

    • No:21402
    • Release Date:2018/08/22 16:27
  • Control cable between high power factor converter and inverter

    Connect the high power factor converter and inverter directly with a control cable, without using a relay. Since a fast-response is required to shut off the ... More Details >>

    • No:21555
    • Release Date:2018/08/22 16:28
  • Influence on leakage current

    Since the converter in the high power factor converter section performs PWM switching, the leakage current increases to the same level as the general-purpose... More Details >>

    • No:21558
    • Release Date:2018/08/22 16:28
  • Regenerative power flow

    If all inverters are in regenerative operation, the regenerative power is regenerated to the power supply. If one of the inverters is power driving, the rege... More Details >>

    • No:21564
    • Release Date:2018/08/22 16:28
  • Inverter selection when multiple inverters are to be connected

    Be sure to use a high power factor converter with the capacity higher than the total capacity of the inverters connected. (Note: One or more of the inverters... More Details >>

    • No:21565
    • Release Date:2018/08/22 16:28
  • Waveform improvement

    A reference sine wave signal is generated inside the high power factor converter, and transistors are configured and PWM switching is performed in the conver... More Details >>

    • No:21574
    • Release Date:2018/08/22 16:28
  • Fault output terminal load pattern

    The fault output terminals A and C, and B and C of the power regeneration converter FR-RC are not capable of a micro load of 5 VDC±5%, 10 mA. The minimum loa... More Details >>

    • No:21966
    • Release Date:2018/08/22 16:30
  • Phase detection terminal

    The phase detection terminal has been provided with units produced since December 1999. You can identify these units with the serial number "N9Z○○○○○○" or la... More Details >>

    • No:22090
    • Release Date:2018/08/22 16:30
  • FR-PU07BB

    Because the internal reset processing is performed when the power supply is turned OFF, the fault state cannot be held. The details of the faults are saved i... More Details >>

    • No:20942
    • Release Date:2018/08/22 16:25