Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ Options ]

21-30 of Total 129

prev 3 / 13page next
  • Replacement of FR-Z100 series

    From Z100 to A520: Use the FR-AAT01 to replace the Z100 with the A520. From Z100 to E520: No attachment is available since E520 is a new series. From Z100 to... More Details >>

    • No:21447
    • Release Date:2018/08/22 16:27
  • Countermeasure against harmonics

    Perform calculation given in the harmonic suppression guidelines, and if the limit value is exceeded, you may also need to insert the ACL. Note that you cann... More Details >>

    • No:21465
    • Release Date:2018/08/22 16:27
  • Combination of the FR-F800 and FR-A8TAT

    Yes, it can. For the capacity of 37K or more, use the included bracket for installation. More Details >>

    • No:20841
    • Release Date:2018/08/22 16:24
  • FR-B3

    The carrier frequency for the FR-B3 is 2 kHz. For the low noise type FR-B3-N, it is 14.5 kHz. More Details >>

    • No:21181
    • Release Date:2018/08/22 16:26
  • Synchronous operation of two motors

    When synchronously operating two motors, you need to detect speed from both motors. Each inverter is controlled based on this speed detection signal. As an e... More Details >>

    • No:21540
    • Release Date:2018/08/22 16:28
  • Leakage current of the FR-HAL/FR-HEL

    It is less than 1 mA. More Details >>

    • No:20844
    • Release Date:2018/08/22 16:24
  • FR-CVL

    Keep a clearance of "minimum 10cm each on top and bottom and minimum 5cm each on right and left". More Details >>

    • No:21178
    • Release Date:2018/08/22 16:26
  • FR-A8TAT

    Yes, it does. (There are some restrictions. More Details >>

    • No:21082
    • Release Date:2018/08/22 16:25
  • Power supply capacity

    Since the input power factor is improved to approximately 1, the power supply capacity can be reduced to 2/3 to 3/4 of an inverter without a power factor imp... More Details >>

    • No:21556
    • Release Date:2018/08/22 16:28
  • Line noise filter

    Yes. However, it is difficult to wind the twisted wires because they are thick. More Details >>

    • No:21128
    • Release Date:2018/08/22 16:26

21-30 of Total 129

Inquiries