  • Using both types of power factor improving reactors

    Yes.By using both types of reactors together, you can reduce the outgoing harmonic current.For examples of harmonics reduction, refer to the value in the har... More Details >>

    • No:21995
    • Release Date:2018/08/22 16:30
  • Using a higher grade power factor improving reactor

    Using a reactor under a load lighter than the rated capacity slightly spoils its effect in improving the power factor.Therefore, you should use a reactor wit... More Details >>

    • No:21935
    • Release Date:2018/08/22 16:30
  • FR-HC2

    It bypasses (removes) high-frequency current due to switching that is output by the FR-HC2 to prevent it from being flown into the power supply system as a f... More Details >>

    • No:21152
    • Release Date:2018/08/22 16:26
  • FR-BSF01

    It is not grounded to the enclosure due to the resin coating. More Details >>

    • No:21122
    • Release Date:2018/08/22 16:26
  • Selection method of the FR-ABR

    The multiple rating is adopted from the FR-A800 series and the motor and the inverter are no longer one-to-one. Thus, considering the combination that the mo... More Details >>

    • No:20846
    • Release Date:2018/08/22 16:24
  • FR-HC/FR-HC2

    No, it cannot. Use the FR-HC2 dedicated reactor and outside box. More Details >>

    • No:20807
    • Release Date:2018/08/22 16:24
  • FR-XC

    - Both 200 V and 400 V can be used only with the capacity 22 kW or higher. - The rated current (capacity) is derated. (For the detail, refer to the Instructi... More Details >>

    • No:20802
    • Release Date:2018/08/22 16:24
  • FR-RC selection

    1. The 100% braking torque means the 100% motor rated torque. Do not consider the continuous regenerative driving based on the braking torque. Consider the r... More Details >>

    • No:22023
    • Release Date:2018/08/22 16:30
  • Fault output terminal load pattern

    The fault output terminals A and C, and B and C of the power regeneration converter FR-RC are not capable of a micro load of 5 VDC±5%, 10 mA. The minimum loa... More Details >>

    • No:21966
    • Release Date:2018/08/22 16:30
  • Size

    The high power factor converter itself is almost same size as general-purpose inverter with the same capacity (FREQROL-A200 series), however, an additional s... More Details >>

    • No:21571
    • Release Date:2018/08/22 16:28