FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > Options
FAQ
Keyword Search
FAQ within [ Options ]
-
The power of MC1 is supplied from the terminals across R2 and S2 of the outside box. Either phase of R2 or S2 may be lost. More Details >>
- No:21146
- Release Date:2018/08/22 16:26
-
A1: Blue, A2: White (transparent) More Details >>
- No:20947
- Release Date:2018/08/22 16:25
-
If all inverters are in regenerative operation, the regenerative power is regenerated to the power supply. If one of the inverters is power driving, the rege... More Details >>
- No:21564
- Release Date:2018/08/22 16:28
-
It is possible when Pr.23 = 0 (Current limit at regenerative driving). More Details >>
- No:20826
- Release Date:2018/08/22 16:24
-
Using a higher grade power factor improving reactor
Using a reactor under a load lighter than the rated capacity slightly spoils its effect in improving the power factor.Therefore, you should use a reactor wit... More Details >>
- No:21935
- Release Date:2018/08/22 16:30
-
To almost "1". (With load factor of 100%) More Details >>
- No:21577
- Release Date:2018/08/22 16:28
-
Yes, it does. (There are some restrictions. More Details >>
- No:21082
- Release Date:2018/08/22 16:25
-
If multiple line noise filters are wound without clearance between them, the noise reduction effect corresponding to the number of filters cannot be obtained... More Details >>
- No:22087
- Release Date:2018/08/22 16:30
-
The high power factor converter itself is almost same size as general-purpose inverter with the same capacity (FREQROL-A200 series), however, an additional s... More Details >>
- No:21571
- Release Date:2018/08/22 16:28
-
Regenerative driving capability
Continuous 100% regenerative braking torque is available for the rated capacity of the high power factor converter. (The same braking ability of the FR-A201 ... More Details >>
- No:21563
- Release Date:2018/08/22 16:28