  • FR-HC2

    Three phases are measured with the CT. The accuracy is ±10 % which is same as the inverter output current. More Details >>

    • No:21145
    • Release Date:2018/08/22 16:26
  • FR-HC2

    The power of MC1 is supplied from the terminals across R2 and S2 of the outside box. Either phase of R2 or S2 may be lost. More Details >>

    • No:21146
    • Release Date:2018/08/22 16:26
  • FR-HC2

    Check that not only the current but also the various elements of the fuse such as cut-off speed and life are equivalent to those of the recommended product. More Details >>

    • No:21153
    • Release Date:2018/08/22 16:26
  • Countermeasure against harmonics

    Perform calculation given in the harmonic suppression guidelines, and if the limit value is exceeded, you may also need to insert the ACL. Note that you cann... More Details >>

    • No:21465
    • Release Date:2018/08/22 16:27
  • Power supply capacity

    Since the input power factor is improved to approximately 1, the power supply capacity can be reduced to 2/3 to 3/4 of an inverter without a power factor imp... More Details >>

    • No:21556
    • Release Date:2018/08/22 16:28
  • Combination with power factor improving reactor

    It cannot be combined with the power factor improving reactor. (Since the power factor is further improved by the high power factor converter, it is not requ... More Details >>

    • No:21560
    • Release Date:2018/08/22 16:28
  • Inverter selection when multiple inverters are to be connected

    Be sure to use a high power factor converter with the capacity higher than the total capacity of the inverters connected. (Note: One or more of the inverters... More Details >>

    • No:21565
    • Release Date:2018/08/22 16:28
  • Leakage current of the FR-BIF

    For the 200 V type, the leakage current at the delta connection is 5 mA. For the 400 V type, it is 10 mA. More Details >>

    • No:20835
    • Release Date:2018/08/22 16:24
  • FR-HAL/HEL

    For 200 V: The cover is attached for 15 K or lower. No cover is attached for 18.5 K or higher. For 400 V: The cover is attached for 55 K or lower. No cover i... More Details >>

    • No:20988
    • Release Date:2018/08/22 16:25
  • FR-HAL

    The UL94V-0 flammability standard is satisfied. More Details >>

    • No:20990
    • Release Date:2018/08/22 16:25