Leakage current of the FR-HAL/FR-HEL
It is less than 1 mA. More Details >>
- No:20844
- Release Date:2018/08/22 16:24
-
It is 0.88 mm2 (AWG18), and 0.3 mm2 (AWG24) for the thermostat. More Details >>
- No:21147
- Release Date:2018/08/22 16:26
-
1. As the reactor (FR-HCL) is connected when connecting the FR-HC, do not connect the FR-BAL. 2. The noise filter can be connected to the input side of the F... More Details >>
- No:22101
- Release Date:2018/08/22 16:30
-
For the products written in the FR-HEL Instruction Manual, the installation of a reactor is required and inverter + reactor is certified as UL standards. For... More Details >>
- No:20944
- Release Date:2018/08/22 16:25
-
When the protective function works, the inverter is stopped (output shutoff) by the RDY signal. More Details >>
- No:21570
- Release Date:2018/08/22 16:28
-
Because RSO (converter reset) of the HC2 is connected to RES of the inverter, the inverter is reset along with the HC2 reset. (Refer to the wiring diagram in... More Details >>
- No:20948
- Release Date:2018/08/22 16:25
-
Since the input power factor is improved to approximately 1, the power supply capacity can be reduced to 2/3 to 3/4 of an inverter without a power factor imp... More Details >>
- No:21556
- Release Date:2018/08/22 16:28
-
Yes, it is. More Details >>
- No:20968
- Release Date:2018/08/22 16:25
-
Inverter selection when multiple inverters are to be connected
Be sure to use a high power factor converter with the capacity higher than the total capacity of the inverters connected. (Note: One or more of the inverters... More Details >>
- No:21565
- Release Date:2018/08/22 16:28
-
The power factor is 0.99 or more (at rated load). More Details >>
- No:20803
- Release Date:2018/08/22 16:24