FAQ within [ FREQROL-A800 ]

91-100 of Total 142

prev 10 / 15page next
  • PLC function

    The number of timer points is 16 for the high speed and low speed in total. More Details >>

    • No:21056
    • Release Date:2018/08/22 16:25
  • Monitoring function of the FR-A800-R2R

    No, they cannot be monitored when Pr.363 is other than "5". They are enabled only when Pr.363 = 5. More Details >>

    • No:20915
    • Release Date:2018/08/22 16:25
  • Carrier frequency automatic reducing function

    The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>

    • No:20903
    • Release Date:2018/08/22 16:25
  • FR-A800-GF/FR-A800-E

    Yes, they can. More Details >>

    • No:20856
    • Release Date:2018/08/22 16:24
  • FR-A800

    Number of terminals: There are the same output terminals as A700 and the following terminals (2 points) are added. Safety: SO, SOC * The terminals SO and SOC... More Details >>

    • No:21098
    • Release Date:2018/08/22 16:25
  • USB version

    Ver1.1 (Ver2.0 (full speed) compatible). USB1.1 supports Full Speed (12 Mbps) and Low Speed (1.5 Mbps) transmission speed modes. USB2.0 supports High Speed (... More Details >>

    • No:21096
    • Release Date:2018/08/22 16:25
  • FR-A800

    The operation panel is also compatible with the IP55 More Details >>

    • No:21091
    • Release Date:2018/08/22 16:25
  • PLC function

    The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>

    • No:21048
    • Release Date:2018/08/22 16:25
  • Error at USB parameter copy

    This error occurs when the parameter file is broken. More Details >>

    • No:20937
    • Release Date:2018/08/22 16:25
  • FR-A800-R2R

    When the value is written to Pr.646 (Stored winding diameter), the stored value is used. When the value is not written, the minimum or maximum winding diamet... More Details >>

    • No:20887
    • Release Date:2018/08/22 16:24