  • FR-A800-E

    It indicate that the actual number of connectable units differs depending on the master side specification although the maximum number of connectable units o... More Details >>

    • No:20839
    • Release Date:2018/08/22 16:24
  • Switching time of the FR-A800 control

    20 ms or less is required to switch the control with the MC signal. More Details >>

    • No:20838
    • Release Date:2018/08/22 16:24
  • FR-A8TAT

    Yes, it does. (There are some restrictions. More Details >>

    • No:21082
    • Release Date:2018/08/22 16:25
  • Frequency search

    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • FR-A800-R2R

    If Pr.361 = 0, the second terminal can be used as the line speed command when X114 is ON, and as the frequency setting value when X114 is OFF. If Pr.361 = 3,... More Details >>

    • No:20891
    • Release Date:2018/08/22 16:24
  • FR-A800-R2R

    The encoder feedback is always required for the thickness calculation function. The actual line speed calculation function requires the input of the actual l... More Details >>

    • No:20890
    • Release Date:2018/08/22 16:24
  • FR-A800-E

    The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>

    • No:20882
    • Release Date:2018/08/22 16:24
  • PLC function

    The processing speed, scan time, and others are slower than those of the programmable controllers. There are some restrictions in the number of I/O points, p... More Details >>

    • No:21103
    • Release Date:2018/08/22 16:25
  • PLC function

    No. To set the PLC function, FR Configurator2 is required. (However, the setting cannot be configured with the trial version.) More Details >>

    • No:21102
    • Release Date:2018/08/22 16:25
  • Combination of the FR-A800 and MM-BF

    Select the models so that "MM - BF rated current value × 1.05 < FR-A820 rated output current value". More Details >>

    • No:21000
    • Release Date:2018/08/22 16:25