Combination of the FR-A800 and MM-BF
Select the models so that "MM - BF rated current value × 1.05 < FR-A820 rated output current value". More Details >>
- No:21000
- Release Date:2018/08/22 16:25
-
It is possible when the dancer control and tension sensor feedback speed control is used and the PID calculation is turned OFF. Because the PID compensation ... More Details >>
- No:20889
- Release Date:2018/08/22 16:24
-
Available under vector control with an encoder.* Zero speed and servo lock are available under PM sensorless vector control only in combination with an MM-CF... More Details >>
- No:21100
- Release Date:2018/08/22 16:25
-
Fuses are not required as peripheral devices for the FR-A802, which has internal fuses. More Details >>
- No:21019
- Release Date:2018/08/22 16:25
-
When the online auto tuning (magnetic field observer) is enabled, the monitoring accuracy is ± 10%. More Details >>
- No:20981
- Release Date:2018/08/22 16:25
-
It is based on the maximum value that can be set for frequency. Specifically, it is 400 Hz. More Details >>
- No:20979
- Release Date:2018/08/22 16:25
-
UVT will occur when reactor is not connected. Always connect a reactor that matches the motor capacity. More Details >>
- No:20978
- Release Date:2018/08/22 16:25
-
The gain of the tension PI gain automatic tuning is the one of the dancer feedback speed control. The gain adjusted by speed control P gain compensation is t... More Details >>
- No:20925
- Release Date:2018/08/22 16:25
-
The output turns OFF (0 mA) during the inverter reset. More Details >>
- No:20921
- Release Date:2018/08/22 16:25
-
It is available if the CC-Link option of the FR-A8NC is installed. More Details >>
- No:20894
- Release Date:2018/08/22 16:24