  • Anti-sway control

    No, it does not affect the control. When a swinging frequency is set in Pr.1074, the setting values in Pr.1077 to Pr.1079 are not referred. When Pr.1074 is s... More Details >>

    • No:20952
    • Release Date:2018/08/22 16:25
  • Frequency setting increment

    The value is displayed in 0.1 rpm increments under Vector control. However, the value is rounded down to the first decimal place and displayed in 1 rpm incre... More Details >>

    • No:21021
    • Release Date:2018/08/22 16:25
  • FR-A800

    When the online auto tuning (magnetic field observer) is enabled, the monitoring accuracy is ± 10%. More Details >>

    • No:20981
    • Release Date:2018/08/22 16:25
  • Storage area

    The storage areas for the sequence programs and for the parameters of the inverter are different. More Details >>

    • No:20958
    • Release Date:2018/08/22 16:25
  • Monitoring function of the FR-A800-R2R

    No, they cannot be monitored when Pr.363 is other than "5". They are enabled only when Pr.363 = 5. More Details >>

    • No:20915
    • Release Date:2018/08/22 16:25
  • PLC function

    Vector control: The SM1217 turns ON when the motor rotates even if no forward rotation command is send. Other than vector control: The SM1217 turn ON by forw... More Details >>

    • No:20907
    • Release Date:2018/08/22 16:25
  • Emergency stop of the FR-A800

    For the V/F control and Advanced magnetic flux vector control, the FR-A800 stops only by Pr.1103 Deceleration time at emergency stop. Pr.815 is not affected. More Details >>

    • No:20860
    • Release Date:2018/08/22 16:24
  • Switching time of the FR-A800 control

    20 ms or less is required to switch the control with the MC signal. More Details >>

    • No:20838
    • Release Date:2018/08/22 16:24
  • Vector control

    Both settings of Pr.83 and Pr.84 are enabled immediately. However, the output voltage is not changed because the value of Pr.83 has little influence on Vecto... More Details >>

    • No:21022
    • Release Date:2018/08/22 16:25
  • FR-A800

    UVT will occur when reactor is not connected. Always connect a reactor that matches the motor capacity. More Details >>

    • No:20978
    • Release Date:2018/08/22 16:25