FAQ within [ FREQROL-A800 ]

111-120 of Total 142

prev 12 / 15page next
  • Switching time of the FR-A800 control

    20 ms or less is required to switch the control with the MC signal. More Details >>

    • No:20838
    • Release Date:2018/08/22 16:24
  • Power supply harmonics countermeasure

    Use a high power factor converter FR-HC2 or reactor as needed. More Details >>

    • No:21115
    • Release Date:2018/08/22 16:26
  • FR-A842

    The inrush current limit circuit is not built in the FR-A842 (inverter unit). It is built in the FR-CC2 (converter unit), which is combined with the FR-A842.... More Details >>

    • No:21059
    • Release Date:2018/08/22 16:25
  • PLC function

    SD1148 can turn ON multiple bits such as STF and RH simultaneously. SM turns ON bits individually. When SD1148 is H5, it is same as when SM1200 (STF) and SM1... More Details >>

    • No:21057
    • Release Date:2018/08/22 16:25
  • Gain adjustment under the speed control

    Since the lower limit has been internally set, 3% or less is recognized as 3%. More Details >>

    • No:21016
    • Release Date:2018/08/22 16:25
  • Reduced impact restart

    Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>

    • No:20904
    • Release Date:2018/08/22 16:25
  • FR-A8AZ

    Not available. When using the motor thermistor function, use the dedicated motor V5RU with a thermistor. More Details >>

    • No:21003
    • Release Date:2018/08/22 16:25
  • FR-A800-R2R

    Basically, it depends on machine specifications. Advantage of dancer feedback speed control: Easy control. Small tension can be controlled. Disadvantage: Mac... More Details >>

    • No:20973
    • Release Date:2018/08/22 16:25
  • Anti-sway control

    No, it does not affect the control. When a swinging frequency is set in Pr.1074, the setting values in Pr.1077 to Pr.1079 are not referred. When Pr.1074 is s... More Details >>

    • No:20952
    • Release Date:2018/08/22 16:25
  • PLC function

    No. To set the PLC function, FR Configurator2 is required. (However, the setting cannot be configured with the trial version.) More Details >>

    • No:21102
    • Release Date:2018/08/22 16:25